Input | |
---|---|
Sensor supply US | 24 V DC (EN 61131-2), max. 500 mA (M12 female), short-circuit and overload protected |
Type | for 3-wire sensors or mechanical switches, PNP, IO-Link Devices |
Connections | |
Fieldbus | Ethernet 10/100 Mbit/s{} M12, D-coded |
Sensor-system/actuator supply | M12 Power, 5-pole, L-coded |
I/O ports | M12, 5-pole, A-coded |
General data | |
Protection | IP67 |
Mounting method | 2-hole screw mounting |
Dimensions H ? W ? D | 43.1?30?225 mm |
Temperature range | -20...+70 °C |
EtherNet/IP | |
Addressing | DHCP, BOOTP or IP address by rotary switch |
DLR (Device Level Ring) | yes |
PROFINET | |
Addressing | DCP |
Shared Device/Input | yes, for 2 controls |
PROFINET Netload Class | II |
Specification | V2.3, Conformance Class C (IRT) |
MRP | yes |
IO-Link | |
IO-Link | 8 ? Master |
Operating modes | COM1{} COM2{} COM3 (automatic) |
Transfer parameters | 32 Input byte and/or 32 Output byte (per IO-Link port) |
Port Class | 4 ? A (port X1...X4), 4 ? B (port X5...X8, galvanically separated, max. 4 A per module) |
Specification | IO-Link Master V1.1 |
Output | |
Actuator supply UA | 24 V DC (EN 61131-2), max. 9 A |
Switching current per output | max. 0.5 A (PIN 4, X1...X8), short-circuit and overload protected |
Parameterization | |
PIN 4 | Input (port X1...X8){} Output (port X1...X8){} IO-Link Master (port X1...X8) |
PIN 2 | Input (port X1...X4) |
Diagnostic | |
Communication status | via LED |
Diagnostic via LED | per module and channel |
Diagnostic via BUS | per module and channel |
Monitoring - under voltage | yes |
Monitoring - no voltage | yes |
Short-circuit and overload | yes |
Actuator warning | via LED and BUS |
Cable break | per port |
Commercial data | |
country of origin | DE |
customs tariff number | 85389099 |
EAN | 4048879727693 |